There are currently millions of Texans wondering what the  ****  happened to the power grid this week. Across Enverus’ Texas workforce, hundreds of us were impacted and want to know what went wrong, too.

In a world of overflowing opinions and speculations on what caused the massive failure to ERCOT’s supply, we want to provide a full explanation of what unfolded from the power market and trading perspective.

Starting with a broad overview from the PUCT, here’s a recap of what happened leading up to the widespread power outages:

“The Polar Vortex unleashed a polar airmass that has settled on much of the Nation and has brought historically low temperatures to Texas. This frigid airmass, in combination with other weather systems, has produced historically low temperatures, ice storms, and record snow falls. Governor Greg Abbott on February 12, 2021 certified that this severe winter weather poses an imminent threat of widespread and sever property damage, injury, and loss of life due to prolonged freezing temperature, heavy snow, and freezing rain statewide. To address this threat, the Governor Abbott declared a state of disaster in all 254 counties of Texas and suspended upon his approval regulatory matters that would hinder or delay necessary action to cope with this disaster. These severe weather events and other events have affected many things, including the wholesale price of electricity and the price of natural gas, a major fuel for electric generation. The effect has been curtailments of the electric-generation fleets committed to the electricity market in the region of the Electric Reliability Council of Texas (ERCOT). The lack of sufficient generation resources caused ERCOT to issue an Emergency Energy Alert 3, which resulting in the shedding of customer load.”

ERCOT Power Grid Issue 1: Gas Supply Prior to the Event

  • Going into the weekend, spot gas prices rose to historic levels due to pipeline transport limitations due to cold temperatures, icy roads in the Permian Basin, freeze-offs impacting producing wells and midstream infrastructure, and power outages impacting infrastructure facilities.
  • This caused the marginal price of energy to increase to extremely high levels on Saturday and Sunday across the US. For ERCOT a $150/MMBtu spot Houston gas with the typical marginal heat-rate for this time of year of 9.2, price power at $1,380/MWh. This is without scarcity pricing adders from the ORDC. Gas prices reached several hundred dollars and topped out at $999 for certain locations in the cash market during this event, according to NGI.
  • The natural gas pipeline flow data has dropped about 4.6 Bcf/d over the past several days. Our data sample for Texas dropped from ~7 Bcf/d to 2 Bcf/d at the peak, and there was likely more gas offline on the intrastate pipelines that we can’t isolate to supply outages yet. We included the data from intrastate deliveries onto interstate systems in the chart below, but some of that gas may be redundant flow (captured in the rest of the chart) or gas staying in Texas that would normally be delivered downstream. Gas supply rebounded a 0.70 Bcf/d on 02/18 from the low point on 02/17.

ERCOT Power Grid Issue 2: Outages

Outages: The major cause is lack of supply due to plants in seasonal maintenance outage, low renewable production, and forced outages of available units due to freezing conditions.

  • ERCOT spring outage season was well underway and seasonal maintenance outages were reportedly just over 13.5GW on February 14, 2021 01:00.
  • Enverus renewable forecasts anticipated very weak produc
    tion for the next several days. Although wind over-produced the forecasts early in the day on Monday, the actualized production was still an anemic 3GW around-the-clock. Similarly, solar suffered from very cloudy conditions across the system.
  • Beginning the evening of Sunday February 14, 2021, power plants of all fuel types (renewable, coal, natural gas, and nuclear) began tripping off-line into forced outage. At the event peak on Monday over 20GW had tripped offline.
    • South Texas Project Nuclear Unit 1
      • NRC Report commentary  ”At 0526 [CST] on 02/15/2021, Unit 1 automatically tripped due to low steam generator levels.”
      • The cause was reported to be inlet water failure due to freezing of several feedwater pumps.
    • Commentary on the other fuel type failures
      • The primary causes for thermal unit trips during the last winter emergency event in February 2011 was freezing of water supply (feedwater pumps) and cooling tower sensors freezing causing automatic system shutdowns. These are likely the main causes for failures in this event as well.

ERCOT Power Grid Issue 3: Load (Historically High Demand Event)

Load: A week in advance, Enverus reported to our customers the risk of historically high demand for this event, exceeding the previous winter peak and possibly near summer peak levels.  We warned of freezing turbine blades at windfarms, as well as risks of thermal unit failures due to the temperatures.  We gave an open webinar on February 12 highlighting the potential risks of situation.

  • ERCOT’s previous all-time winter peak demand record was set on Jan. 17, 2018, when demand reached 65,915 MW between 7 and 8 a.m.
  • Due to successive EEA event declarations, demand was not able to reach forecasted levels.
    • “EEA Level 1: At 00:15, ERCOT at EEA 1 – Reserves below 2, 300 MW. No rotating outages at this time.”
    • “EEA Level 2: At 01:07, ERCOT at EEA 2 – Reserves below 1, 750 MW. Load resources are being deployed. There may be a need to implement rotating outages. ERCOT is urging consumers and businesses to reduce electricity usage.”
    • “EEA Level 3 With Firm Load Shed: At 01:20, Rotating outages are in progress to maintain frequency. ERCOT is asking consumers and businesses to reduce electricity use.”

ERCOT Power Grid Issue 4: Congestion

Congestion: As demand increased over the weekend, transmission congestion caused price suppression in areas like the Lower Rio Grande Valley (The Valley). Fast forward to Monday when the power prices went to the $9,000/MWh offer cap and remained there throughout the load shedding event. LMP price spreads collapsed although congestion issues continued to exacerbate grid stability challenges as EEA3 rolling outages began and continued for days.

Complicating Factors in Restoration

The issue throughout this week has been the lack of generating supply. On Monday, some of the units that initially tripped were able to return to service within 24 hours. However, a large portion of thermal generators would not become available until Wednesday morning.

During the time between Monday and Wednesday, ERCOT attempted to return as many customers as possible. ERCOT continuously worked to add meters only to have to cut them again later in the day for system stability.  They contended with low operating reserves, frequency oscillations, and voltage issues from plants attempted to return to service, as well as variable supply from renewable generation.

The fact that the ERCOT operators made the quick call to enter EEA3 operations and shed load when they did, kept the ERCOT grid from a blackout. These operators are the unsung heroes. If a blackout had occurred, it would likely have taken SEVERAL MONTHS to return service to the entire ERCOT footprint.

How did this happen?

A similar event happened during the first week of February 2011. Temperature was anticipated to be near historic lows with strong forecasted demand. During the late hours of February 2, thermal powerplants tripped offline in masse due to the temperatures, causing ERCOT to shed load in an EEA3 emergency.

After the event, regulators required that power plants prepare formal winterization procedures as well as reviewing these procedures on a regular basis.

One of the major factors that separates weatherized plants outside of the southern regions of the country is that the turbines are generally not housed inside a building and are exposed to the elements.  This is due to ERCOT being a summer optimized market.  Building structures around these turbines would generally cause a loss of heat-rate optimization and total output capabilities during the summer.  In fact, cold temperatures are usually of benefit to the Texas thermal generating units’ efficiency.

Additionally, the Texas wind fleet is optimized for the warmer climates as it is rarely cold enough to become an issue. Typically, they do not have anti-icing technology that is seen in colder climates.

Finally, ERCOT has a very small but growing solar fleet which under cloudy conditions was not a major factor in providing capacity through this event.

Watch our on-demand replay where we discussed these issues and more!

Picture of Scott Bruns

Scott Bruns

Scott D Bruns is the Director of Power Markets at Enverus, leading the research division who specialize in analyzing large datasets for informed decision-making. As an expert in the ERCOT market, he provides comprehensive reports on market trends for various stakeholders. Leveraging his background in power trading and asset management, Scott contributes to the development of innovative SaaS products and offers expertise on US power market fundamentals. As an Enverus spokesperson, he guides clients in asset siting, trading optimization, and investment decisions. Prior to joining Enverus, Scott traded power and provided in fundamental analysis at Direct Energy. He holds a bachelor’s degree in mathematics from the University of Houston. When not obsessed with power markets, Scott spends time with his family who provide the inspiration for all his efforts.

Subscribe to the Enverus Blog

A weekly update on the latest “no-fluff” insight and analysis of the energy industry.

Related Content

energy-transition
Energy Analytics Energy Transition
ByEnverus

The energy transition and the drive toward net zero have created a nascent market where investment opportunities, regulations and risks evolve daily.

energy-transition
Energy Transition
ByMarc De Guzman

Natural gas power plants have become increasingly attractive to investors, due to rising load growth expectations and the need for reliable grid balance. With coal plant retirements and a surge in intermittent generation, natural gas is critical for ensuring adequate...

Enverus_Press_Release_EV_Regional_Volatility_Thumbnail
Power and Renewables
ByDavid Watson

As the process to successfully build profitable renewable assets becomes more challenging, the need for accurate and up-to-date data on the power grid is needed more than ever.

bA
Financial Services Operators
ByEnverus

Energy Stakeholders Meet in New Mexico to Address Key Permian Basin Issues Last month, stakeholders from across the energy sector gathered in New Mexico to tackle the pressing issues facing the Permian Basin. Among the wide-ranging discussions, three key themes...

Enverus Press Release - Heightened natural gas price volatility expected amid supply and demand challenges
Oilfield Services
ByAdriana Bickford

In today’s oil and gas industry, standing out and securing visibility with operators has become increasingly challenging.  As traditional marketing channels lose their effectiveness, oilfield service providers are left looking for powerful ways to showcase their strengths and seize valuable...

Enverus Blog - Oil and gas procurement automation: End project delays and overspending
Operators
ByEnverus

Multilateral wells have transformed Canada's Clearwater and Lloydminster Mannville plays, among others, into some of the best resource plays in North America today.

energy-transition
Energy Transition
ByChris Griggs

With 2025 less than two months away, it's time to prepare yourself with key energy insights and the latest energy trends for the new year. The highlight anticipated Enverus e-book, slated for release in early January 2025, has the energy community buzzing. Today,...

Enverus Press Release - Enverus Integrates With Fendahl to Enhance Energy Trading and Risk Management Solutions
Analyst Takes Intelligence
ByAl Salazar, Enverus Intelligence® | Research (EIR) Contributor

The following blog is distilled from an interview on the CBC’s “The Eyeopener,” hosted by Loren McGinnis who interviewed Enverus Intelligence® Research’s very own Al Salazar. Click here to listen to the full radio segment.  In its recent World Energy...

bA
Oilfield Services
ByMac Graham

Make strategic supply chain decisions faster with data in a single source-to-pay platform In the world of oil and gas, the importance of data and efficient supply chain management cannot be overstated. These elements are the backbone of successful operations,...

Let’s get started!

We’ll follow up right away to show you a quick product tour.

Let’s get started!

We’ll follow up right away to show you a quick product tour.

Sign up for our Blog

Register Today

Sign Up

Power Your Insights

Connect with an Expert

Access Product Tour

Speak to an Expert